2491X
2491X
  • 1 -
    Class 5 Copper Conductor
  • 2 -
    PVC Insulation
Operating Temperature
Class V Flex
Flame Retardant
Lead - Free

 

Standard
TS EN 50525-2-31, HD 21.3 S3, BS 6004, VDE 0281
 
Technical Data
Max.Operating Temperature : 70 °C
MAx.Short Circuit Temperature : 160°C
Rated Voltage : 450/750 V
 
Application
For protected installation and lighting fitting.Also for in conduit, on and under plaster.

 

Nominal
Cross Section
Diameter
(App.)
Total Weight
(App)
Delivery
Lenght
Resistance at 20°C Current Carying Capacity
mm² mm kg/km m ohm/km Boruda 20°C de A Havada 30°C de A
1,5 3 20 100 13,3 15 24
2,5 3,6 32 100 7,98 20 32
4 4,2 48 100 4,95 25 42
6 4,8 68 100 3,3 33 54
10 6,7 116 100 1,91 45 73
16 7,9 174 100 1,21 61 98
25 9,7 270 1000 0,78 83 129
35 11,1 368 1000 0,554 103 158
50 13,3 524 1000 0,386 132 198
70 15,2 717 1000 0,272 165 245
95 17,7 971 1000 0,206 197 292
120 19,6 1212 1000 0,161 235 344
150 21,9 1514 1000 0,129 391
185 24,3 1869 1000 0,106 448
240 27,5 2415 1000 0,0801 528