CU/PVC/AWA/PVC
Cu/PVC/AWA/PVC
Cu/PVC/AWA/PVC
  • 1 -
    Class 2 Copper Conductor
  • 2 -
    PVC Insulation
  • 3 -
    PVC Filler
  • 4 -
    Aluminium Wire
  • 5 -
    PVC Sheath
Operating Temperature
Class I
Class II
Flame Retardant
Lead - Free

 

Standart
TS IEC 60502-1, IEC 60502, VDE 0276
 
Technical Data
Max.Operating Temperature : 70 °C
Max.Short Circuit Temperature : ≤ 300 mm² 160°C , >300 mm² 140 °C
Rated Voltage : 600/1000 V
 
Application
Is most suitable in areas where mechanical damage is a possibility.İs laid outdoors, indoors, underground and in ducts.I requested can be produced to resist saline environment.
 

 

Nominal
Cross Section
Diameter
(App.)
Total Weight
(App)
Delivery
Lenght
Resistance at 20°C Current Carying Capacity
mm² mm kg/km m ohm/km Toprakta 20°C de A Havada 30°C de A
1x10 13,5 290 1000 1,83 78
1x16 14,5 380 1000 1,15 127 103
1x25 15,9 500 1000 0,727 163 137
1x35 17 610 1000 0,524 195 169
1x50 19,5 810 1000 0,387 230 206
1x70 20,9 1050 1000 0,268 282 261
1x95 23 1350 1000 0,193 336 321
1x120 25,5 1660 1000 0,153 382 374
1x150 27 1970 1000 0,124 428 428
1x185 29,5 2400 1000 0,0991 483 494
1x240 32,5 3050 1000 0,0754 561 590
1x300 35,5 3750 1000 0,0601 632 678
1x400 41,5 4930 1000 0,047 730 817
1x500 45,5 6120 1000 0,0366 823 940
1x630 49 7430 1000 0,0283 866 1108